Power By Terry McCarthy, publisher of Nashville Home Pros Magazine · November 6, 2026 · 5 min read

At 8:19 on the morning of December 23, 2022, the station at Belle Meade read 5 degrees below zero (the Weather Service’s record). A little over an hour later, at 9:31 Central time, the Tennessee Valley Authority ordered part of its load cut off. “This was the first time in TVA’s history that TVA ordered firm load shed,” federal staff wrote afterward (the FERC-NERC inquiry).
Firm load shed is the grid operator’s term. NES’s later account calls the same thing rolling blackouts. It came two days before Christmas, and a bigger order followed the next day. We’ve converted the inquiry’s Eastern times to Central below.
A 46-degree drop in five hours
The wind came first. Nashville International logged a 46 mph gust on the evening of December 22 (the Weather Service’s page). By the next morning Davidson County stations were reading -5 at Belle Meade and at a station two miles west of Nashville, and 0 at another. The airport reported -1, though the Weather Service’s page flags that reading’s timestamp as inconsistent.
The wind chill at John C. Tune Airport and at Vanderbilt was -25. It was -24 in Belle Meade and -22 at the airport. Chills of -15 to -30 were common across the area through December 24.
On the generating side, TVA reported to federal staff “a drop of 46 degrees in five hours.” It told them that rain followed by extreme cold and wind was “beyond the design basis of some TVA generating sites.”
December 23: the first order
By 5 a.m. Central, TVA had lost more than 5,000 megawatts of generation and declared the first two levels of energy emergency (the inquiry’s timeline). At 5:12 it declared the third, Energy Emergency Alert 3, meaning firm load shed was imminent.
Demand set a new winter record that day, 33,425 megawatts. (A table in the same report shows 33,427.) By 9:31, unplanned generation outages stood at 6,500 megawatts, and TVA ordered a cut of about 5% of peak system load, more than 1,500 megawatts. It ordered power restored at 11:43 a.m.
December 24: double the cut
TVA stayed at Energy Emergency Alert 3 until midday on December 24, apart from a brief step down on the afternoon of the 23rd. Before dawn Nashville International was at 5 degrees, at 5:53 a.m., with other Davidson County stations between 3 and 7.
Early that day came a second order: 5%, then another 5%, for a total of 10% of peak load, “over 3,000 MW.” It went to TVA’s 153 local power companies, which together serve 10 million people in Tennessee and parts of six other states. The inquiry’s table lists TVA at seven hours of load shed. The firm load cut across the entire Eastern Interconnection was 5,411.6 megawatts, so TVA’s share was more than half.
More than half of the firm load cut across the whole Eastern Interconnection was TVA’s.
The record doesn’t reach down to any one house. We couldn’t find NES’s own numbers for those two days. The customer counts and outage intervals that circulate came from TV news, so they aren’t here. TVA’s After Action Report sits on a site that blocked our access, which means TVA’s account in this story is the one federal staff quote.
What the agencies say changed
NES draws a straight line from that week to the next hard winter. “In 2022, after Winter Storm Elliot forced TVA into rolling blackouts,” its 2024 annual report says, the utility took two lessons: control-room sophistication that kept the network intact, and more transparency with customers. In the January 2024 winter storm, it reports, 20,449 customers had an interruption, never more than 2,250 at once, and it “successfully avoided another round of rolling blackouts.”
TVA told federal staff it put “approximately $100 million” into sturdier protections and hardening for its generators (the Winter 2026 review). Generator outages in January 2026 ran roughly 45 minutes to four hours, “as opposed to days,” and there was no manual load shed in that cold spell. Its load forecast error fell from 4.25% during Elliott to 2.73% in January 2025, when it also stationed gas liaisons at generators around the clock in extreme cold and again shed no load (the January 2025 review).
Those are TVA’s numbers, as reported to its regulators, and the same 2026 document carries a reminder. Winter Storm Fern still caused widespread outages for TVA customers through damage to distribution and transmission, including 38 transmission lines. A grid with enough generation doesn’t help a street whose line is down.
Running a generator at home
For a house with a portable generator, that’s when the safety numbers matter. The Consumer Product Safety Commission says about 100 people in the U.S. die each year of carbon monoxide poisoning from portable generators. Its 2022 report put the figure at about 85 a year for 2017 through 2019, a different period, and found 81% of those deaths in residential locations.
NES’s page doesn’t go on to explain transfer switches, and we couldn’t find that language at CPSC or the Weather Service, so we won’t spell out a rule for it. Put the question to the power company before anyone wires anything. If your bill comes from a company other than NES, in Gallatin, Lebanon or Spring Hill, ask that company the same thing; its lines have lineworkers on them too.
Sources
- FERC and NERC staff: Inquiry into Bulk-Power System Operations During December 2022 Winter Storm Elliott
- FERC: January 2025 Arctic storms performance review
- FERC and NERC staff: Winter 2026 Arctic Events
- National Weather Service, Nashville: December 22-24, 2022 arctic outbreak
- Nashville Electric Service: 2024 Annual Report
- Nashville Electric Service: Electrical safety at home
- U.S. Consumer Product Safety Commission: CPSC safety tips on carbon monoxide poisoning and fires in winter storms, 2026
- U.S. Consumer Product Safety Commission: New report on carbon monoxide fatalities, 2022
This story runs online only. Every fact in it is linked to the page it comes from, read on November 6, 2026. See something that has changed? Send us a note.